Skip to content

Electrical enclosures used in demanding environments need more than a suitable normal housing material. Their surface finish also has a role in protecting the enclosure, supporting the durability of the assembly and maintaining a consistent appearance over time.

For aluminium enclosures, this starts before the final colour is applied. The coating specification supplied combines a chromate conversion pre-treatment with a polyester powder coating. Each stage has a distinct purpose: the pre-treatment prepares the aluminium surface, while the powder coating provides the durable outer finish.

Preparing the Aluminium Surface

The specification calls for a chromate conversion treatment for aluminium and aluminium alloys. This produces a surface with corrosion resistance and provides a sound base for paint adhesion.

The conversion film also has low electrical resistance. That matters for electrical equipment because the treatment can be used with negligible effect on earth bonding. Depending on the process, the treated surface may range in appearance from colourless to deep bronze before the final coating is applied.

Good preparation is particularly important where an enclosure will be exposed to moisture, changing temperatures or other demanding conditions. The performance of the finished coating depends on the condition of the surface beneath it, as well as on the coating itself.

Applying the Polyester Powder Coating

The specified D1036 Fiji polyester powder coating is applied by electrostatic spraying. Dry powder is deposited on to the enclosure, which then passes through an oven. Heat melts the powder so that it flows across the surface, before curing into a hard finish.

Unlike a conventional wet paint system, the powder coating does not rely on solvents during application. The specification describes a single powder application producing a tough, cohesive coating. Its stated film thickness is 70–90 microns, with an operating temperature of up to 120°C. The curing schedule depends on the mass of the component; the specification gives 200°C for 20 minutes as a guide.

These details matter when coating enclosures with different sizes, shapes and wall thicknesses. Consistent application and appropriate curing help achieve the intended finish across the component.

How Is the Finish Assessed?

The specification includes laboratory test results covering adhesion, hardness, flexibility and impact resistance. It also records performance under salt spray, constant humidity, sulphur dioxide and accelerated weathering tests.

For example, the coating achieved a Gt 0 adhesion result in the specified crosshatch test. The documented salt spray and constant humidity tests each ran for 1,000 hours, against the acceptance criteria set out in the specification. These results provide useful evidence when assessing the finish for an enclosure application.

Laboratory results are a guide rather than a guarantee of service life. Actual performance depends on factors such as the installation environment, the enclosure design, handling and maintenance.

Why the Transition Matters

The SPB range has been reviewed for suitability against original application requirements and is considered technically acceptable for continued operational use, subject to project-specific engineering review where required.

Considering the Complete Enclosure

A surface finish should be considered alongside the rest of an enclosure’s design. Material selection, cable entries, seals, fixings and the intended installation conditions all influence how an electrical assembly performs in service.

For JCE, the coating specification is one part of delivering an enclosure suited to its application. Understanding the pre-treatment, coating process and supporting test data helps customers make informed decisions about finishes for electrical equipment operating in demanding environments.

If you are specifying an enclosure for a particular project, contact JCE to discuss the environmental conditions, finish requirements and additional coating processes available, alongside the wider electrical and mechanical design.

Case Studies

Bespoke Modular Solar Power Solution

Designing and delivering a custom solar power system for hazardous zones, enabling safe, off-grid energy in extreme conditions.

Solar Power System for South N'dola Wellhead Platform

Supplying a bespoke solar power system for the South N'dola wellhead platform to support safe, reliable offshore energy.

Level Gauging System: Enhancing Safety and Efficiency for Gas Bottling Plant

Designing a custom level gauging system to enhance safety, accuracy, and operational efficiency at a gas bottling plant.

Get In Touch

JCE Group (UK) Ltd

Blackburn Business Park
Aberdeen, AB21 0PS
United Kingdom

JCE Energy Ltd

Blackburn Business Park
Aberdeen, AB21 0PS
United Kingdom

JCE (Europe) Ltd

East Way, Lee Mill Industrial Estate,
Ivybridge, Devon, PL21 9LL
United Kingdom

JCE Group (EspaƱa) SL

No 1, Avenida Europa
San Eugenia Alto
38660 Adeje, Tenerife,
Spain

Submit An Enquiry