This informative piece takes a dive into the integration of Fuel Cells within JCE’s hybrid system philosophy, highlighting a number of scenarios and the advantages/disadvantages they bring to the overall system.

Power Requirements

Power:180W, Continuous 24Vdc, 24 h/day
Battery:VRLA, 4 days autonomy
System Recharge Time:4 days
Location:Safe Area
Geography:North Sea

Overall System Philosophy

 Solution 1:
System completely powered by solar panels and batteries.


Solution 2:
System powered by solar panels, batteries and fuel cells.
Solution 3:
System powered by solar panels, batteries and fuel cells with additional autonomy.

Solar Panels:461512
Battery:1 x 1200 Ah@24Vdc1x 1200 Ah@24Vdc1 x 600 Ah@24 Vdc
Fuel Cells:06 x 195 W Fuel Cell3 x 195 W Fuel Cell
Installation Footprint:70m220m216m2
System Weight:3 Tons2.2 Tons1.7 Tons
CAPEX Price (£):19,00023,50012,900
OPEX Cost (£/annual):9001,3001,600
Fuel Cost (£/annual):0400700
System Availability:99.5%99.8%99.99%
Availability Explanation:The system availability is the lowest due to the dependence on weather conditions.The system availability is justified due to the fuel cell offering back-up capacity for the system.The system availability is justified due to the increased number of fuel cells offering back-up capacity for the system.
Advantages + + Self sustained off-grid solution
+ Reduced O&M cost
+ No fuel
+ Long system life-time (15 years)
 Self-sustained off-grid solution
+ Reduced O&M cost
+ Silent
+ Long system life-time (15 years)
+ Increased system availability (less weather dependent)
+ Reduced installation footprint
+ Reduced design activities (standard solutions available) 
+ Self-sustained off-grid solution
+ Reduced O&M cost
+ Low CAPEX costs
+ Silent
+ Long system life-time (15 years)
+ Increased system availability (not weather dependent)
+ Extremely reduced installation footprint/weight
+ Reduced design activities (standard solutions available)
Disadvantages – System availability is weather dependent.
– Installation footprint must be assessed for each project
– Ad-hoc design required
– High CAPEX costs
– Eco-fuel dependent*
*classed as disadvantage but simple to overcome in line with standard maintenance activities
– Eco-fuel dependent* 
Suitability Examples: – Highly predictable and good weather conditions, e.g. MENA region
– High footprint available 
– Suitable for unpredictable weather conditions, e.g. North Sea/Canada
– Limited footprint available 
– Suitable for unpredictable weather conditions, e.g.
– North Sea/CanadaLimited footprint availableHigher system availability and autonomy requirements

Case Studies

Bespoke Modular Solar Power Solution

Designing and delivering a custom solar power system for hazardous zones, enabling safe, off-grid energy in extreme conditions.

Solar Power System for South N'dola Wellhead Platform

Supplying a bespoke solar power system for the South N'dola wellhead platform to support safe, reliable offshore energy.

JCE Level Gauging System: Enhancing Safety and Efficiency for Gas Bottling Plant

Designing a custom level gauging system to enhance safety, accuracy, and operational efficiency at a gas bottling plant.

Get In Touch

JCE Group (UK) Ltd

Blackburn Business Park
Aberdeen, AB21 0PS
United Kingdom

JCE Energy Ltd

Blackburn Business Park
Aberdeen, AB21 0PS
United Kingdom

JCE (Europe) Ltd

East Way, Lee Mill Industrial Estate,
Ivybridge, Devon, PL21 9LL
United Kingdom

JCE Group (España) SL

No 1, Avenida Europa
San Eugenia Alto
38660 Adeje, Tenerife,
Spain

Submit An Enquiry